Safe, Efficient Gas Detection (CO/NO2)

Code & compliance

CO2 detection
for beverage systems.

Restaurants, bars, stadiums, breweries and hotels that run soda or beer off a bulk liquid CO2 tank fall under a specific section of the fire code. CO2 is heavier than air, so a leak in a basement, a walk-in or a back room pools at floor level and displaces oxygen without any smell. The code answer is either mechanical ventilation or a CO2 gas detection system, and many sites choose detection.

When the requirement applies

The California Fire Code (section 5307.3) and the International Fire Code that most other states adopt (section 5307.5) cover insulated liquid carbon dioxide systems with more than 100 pounds of CO2 used for beverage dispensing. Smaller high-pressure cylinder setups are generally below that line, though your local fire department has the final word. In California, systems over 100 pounds also need a fire department operational permit.

Ventilation or detection

Rooms and areas with the tank, cylinders, piping or equipment, and any area where a leak would collect, need mechanical ventilation designed to keep the room at negative pressure. The code allows a gas detection system instead, which is often simpler than adding exhaust to a basement or walk-in.

What the detection system has to do

  • Sensors low. CO2 sensors go within 12 inches of the floor, in the area where leaking gas is expected to accumulate, or another approved location.
  • 5,000 ppm: supervisory alarm. An audible and visible supervisory alarm at a normally attended location, such as the bar or the manager’s office.
  • 30,000 ppm: local alarm. An audible and visible alarm in the room or immediate area where the system is installed, telling people to get out.
  • Built to section 916. The system must meet the general gas detection rules: equipment designed for CO2, installed to the manufacturer’s instructions, permanent power, and a trouble signal if power is lost.
  • Signs. Fire departments commonly require warning signs at the entrance to the area, telling people not to enter when the alarm is active.

Testing and calibration

Because the system is built to section 916, the same maintenance rule that applies to a parking garage applies here: the system has to be inspected and tested at least annually, and each sensor calibrated at the interval its manufacturer specifies. CO2 sensors are a different technology from the CO sensors in a garage and need their own calibration gas.

Not the same as a garage system

CO2 detection for beverage storage is a separate system from the carbon monoxide detection in a parking garage. If paperwork for a garage says “CO2”, it almost always means CO, see CO vs CO2 vs NO2. If your building has both, one visit can cover both systems, each with the right gas.

Talk to us

Gas monitoring is the only thing we do. Tell us where the CO2 tank is and what detection is installed, or send a photo of the unit, and we will tell you what it needs to meet code.

Common questions

Does a restaurant CO2 tank need a gas detector?

If it is an insulated liquid CO2 system with more than 100 pounds of CO2 used for beverage dispensing, the fire code requires either mechanical ventilation or a CO2 gas detection system in the rooms and areas where the tank, piping and equipment are located and where a leak would accumulate.

At what level does a CO2 alarm go off?

The code sets two levels: a supervisory alarm at a normally attended location at 5,000 ppm, and an audible and visible alarm in the room or immediate area at 30,000 ppm.

Where do CO2 sensors go?

Within 12 inches of the floor, in the area where leaking CO2 is expected to collect, because CO2 is heavier than air. The fire department can approve other locations.

How often does a CO2 detection system need testing?

The system has to be inspected and tested at least annually, and the sensors calibrated at the interval the manufacturer specifies, under the general gas detection section of the fire code (section 916).


Talk to a gas monitoring specialist

Tell us the building and how many sensors you have. We will tell you what service it needs and what it costs, no pressure.